Wire gauge chart (AWG) with amps

Updated · Source : NFPA 70, National Electrical Code (2023), Table 310.16, copper conductors, rates as of

12 AWG wire is 2.053 mm across with a 3.31 mm² cross-section; 14 AWG is 1.628 mm. In homes, 14 AWG copper is protected at 15 A and 12 AWG at 20 A.

AWG wire sizes to scale
AWG 180.82 mm²Ø 1.02 mmAWG 161.31 mm²Ø 1.29 mmAWG 142.08 mm²Ø 1.63 mmAWG 123.31 mm²Ø 2.05 mmAWG 105.26 mm²Ø 2.59 mmAWG 88.37 mm²Ø 3.26 mmAWG 613.3 mm²Ø 4.12 mm1 mmConductor cross-sections at the same scale
Wire gauge chart (AWG) with amps
AWGDiameter (mm)Diameter (in)Area (mm²)Amps 60 °CAmps 75 °CAmps 90 °C
4/011.6840.4600107.219195230260
3/010.4050.409685.029165200225
2/09.2660.364867.431145175195
1/08.2510.324953.475125150170
17.3480.289342.408110130145
26.5440.257633.63195115130
35.8270.229426.67085100115
45.1890.204321.151708595
54.6210.181916.773———
64.1150.162013.302556575
73.6650.144310.549———
83.2640.12858.366405055
92.9060.11446.634———
102.5880.10195.261303540
112.3050.09074.172———
122.0530.08083.309202530
131.8280.07202.624———
141.6280.06412.081152025
151.4500.05711.650———
161.2910.05081.309———
171.1500.04531.038———
181.0240.04030.823———
190.9120.03590.653———
200.8120.03200.518———
210.7230.02850.410———
220.6440.02530.326———
230.5730.02260.258———
240.5110.02010.205———
260.4050.01590.129———
280.3210.01260.081———
300.2550.01000.051———
320.2020.00800.032———
340.1600.00630.020———
360.1270.00500.013———
380.1010.00400.008———
400.0800.00310.005———
Need a value that is not in the table? Open the calculator : Awg Wire Gauge Sizing →

How it is computed

Diameters come from the AWG definition: d = 0.127 mm × 92^((36 − n)/39), where 1/0 counts as 0, 2/0 as −1 and so on; area = π/4 × d². Ampacities are the copper values of NEC Table 310.16 for up to three current-carrying conductors at 30 °C ambient.

FAQ

Why does the table say 25 A for 12 AWG but breakers are 20 A?+

The NEC small-conductor rule (240.4(D)) caps overcurrent protection at 15 A for 14 AWG, 20 A for 12 AWG and 30 A for 10 AWG copper, below the table ampacity.

Which temperature column should I use?+

The lowest rating among the wire, the terminals and the device. Most residential breakers and receptacles are rated 60 °C or 75 °C, so the 90 °C column is mainly a starting point for derating.