Extension cord gauge chart

Updated · Source : NFPA 70, National Electrical Code, Table 400.5(A)(1), rates as of

A 50 ft cord for a 13 A tool needs at least 14 AWG to stay within a 3% voltage drop; a 100 ft cord at 15 A needs 10 AWG, or 12 AWG if you accept 5%.

AWG wire sizes to scale
AWG 180.82 mm²Ø 1.02 mmAWG 161.31 mm²Ø 1.29 mmAWG 142.08 mm²Ø 1.63 mmAWG 123.31 mm²Ø 2.05 mmAWG 105.26 mm²Ø 2.59 mmAWG 88.37 mm²Ø 3.26 mmAWG 613.3 mm²Ø 4.12 mm1 mmConductor cross-sections at the same scale
Extension cord gauge chart
Cord length (ft)5 A7 A10 A13 A15 A20 A
10181818161412
15181818161412
25181818161412
50181614141212
75161412121210
1001414121010—
12514121010——
150121210———
Need a value that is not in the table? Open the calculator : Awg Wire Gauge Sizing →

How it is computed

For each length and current, the table picks the thinnest copper gauge whose cord ampacity covers the load and whose round-trip resistance keeps the drop under the limit at 120 V: drop = amps × resistance of 2 × length ÷ 120. A lower AWG number is a thicker wire. A dash means no common cord gauge meets the limit.

FAQ

Is a thicker cord ever a problem?+

No. A lower AWG number than the table shows is always safe; it only costs more and weighs more.

Can I plug two cords together?+

Avoid it. Each connection adds resistance and heat; use one cord long enough, of the gauge for the total length.